Author(s): Sofia Fellini; Riccardo Vesipa; Fulvio Boano; Luca Ridolfi
Linked Author(s): Sofia Fellini, Riccardo Vesipa
Keywords: Emergency management; Fault isolation; SCADA; Water Supply; Multipurpose water use
Abstract: This work presents an algorithm for real-time fault detection in the SCADA system of a modern water supply system (WSS) in an Italian Alpine Valley. By means of both hardware and analytical redundancy, the proposed algorithm compares data and isolates faults on sensors through the residual analysis. Moreover, the algorithm performs a real-time selection of the most reliable measurements for the automated control of the WSS operations. A coupled model of the hydraulic and remote-control system was developed to test the effectiveness of the proposed algorithm. Simulations showed that error detection and measurement assessment are crucial for the safe operation of the WSS.
Year: 2018